DESCRIPTION
If the cooling effect of the air conditioning system is weak, the following factors may be the cause.
Symptom | Factor |
---|---|
|
|
PROCEDURE
1. | CHECK FOR DTC |
(a) Check for DTCs.
Body Electrical > Main Body > Trouble Codes Result | Proceed to |
---|---|
B124400 is not output | A |
B124400 is output | B |
B | GO TO DTC B124400 |
|
2. | CHECK ECO MODE SETTING |
(a) Check if the ECO mode indicator is off.
OK:
The ECO mode indicator is off.
OK | GO TO STEP 4 |
|
3. | CHECK ECO MODE CONTROL OPERATION |
(a) Operate the ECO switch assembly (air conditioning control assembly) and check that the ECO mode indicator turns off and the blower speed reduction is canceled.
HINT:
Control | Outline |
---|---|
Blower Control | When the air conditioning system is in AUTO mode, the blower speed will be reduced to a certain speed. Additionally, if warm-up control is operating, the blower speed will be further reduced. |
Air Inlet Control | If the ambient temperature is a certain value or more, the air inlet mode will be changed to recirculation mode. |
Result | Proceed to |
---|---|
ECO mode indicator turns off and blower speed reduction is canceled | A |
ECO mode indicator turns off, but the blower speed reduction is not canceled | B |
ECO mode indicator does not turn off | C |
B | REPLACE AIR CONDITIONING AMPLIFIER ASSEMBLY |
C | REPLACE AIR CONDITIONING CONTROL ASSEMBLY |
|
4. | PERFORM REFRIGERANT SHORTAGE CHECK |
(a) Check that the following conditions are met and perform the refrigerant shortage check according to the display on the GTS.
Measurement Condition: Item | Condition |
---|---|
A/C switch | On |
Ambient temperature*1 | 0 to 49°C (32 to 120°F) |
Blower speed | HI |
*1: If the ambient temperature is not within the range shown, do not perform this check.
Body Electrical > Air Conditioner > Utility Tester Display |
---|
Refrigerant Gas Volume Check |
Result | Amount of Refrigerant |
---|---|
Refrigerant correct | Correct |
Refrigerant shortage | Insufficient |
OK:
"Refrigerant correct" is displayed on the GTS.
NG | REPAIR REFRIGERANT LEAK |
|
5. | PERFORM ACTIVE TEST USING GTS (FRONT LEFT AIR MIX DAMPER CONTROL SERVO MOTOR, FRONT RIGHT AIR MIX DAMPER CONTROL SERVO MOTOR) |
(a) Perform the Active Test according to the display on the GTS.
Body Electrical > Air Conditioner > Active Test Tester Display | Measurement Item | Control Range | Diagnostic Note |
---|---|---|---|
Front Left Air Mix Damper Control Servo Motor | No. 1 air conditioning radiator damper servo sub-assembly pulse | Min.: 128 Max.: 384 | - |
Front Right Air Mix Damper Control Servo Motor | No. 1 air conditioning radiator damper servo sub-assembly pulse | Min.: 128 Max.: 384 | - |
Tester Display |
---|
Front Left Air Mix Damper Control Servo Motor |
Tester Display |
---|
Front Right Air Mix Damper Control Servo Motor |
OK:
Each damper servo motor operates.
OK | INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET |
NG | GO TO DTC TROUBLESHOOTING PROCEDURE FOR MALFUNCTIONING DAMPER SERVO MOTOR |